IndustryHub
LERNEN / NORMEN / IEC

IEC 60079-25

⚠ Diese Seite ist noch nicht übersetzt. Anzeige auf Englisch.
IEC 60079-25

Intrinsically Safe Electrical Systems

IEC 60079-25 extends IEC 60079-11 from individual devices to complete intrinsically safe systems (loops, segments). It defines how to combine certified IS components into a documented safe installation.

Dokumentstruktur

IEC 60079-25:2010

Intrinsically safe electrical systems

Bridges device-level IS (IEC 60079-11) to installation-level IS. Defines : entity parameter combination rules, FISCO system design, FNICO for energy-limited fieldbus, IS system documentation requirements.

Schlüsselbegriffe

IS System
A combination of IS-certified components (transmitter, barrier, cable) operating together as an intrinsically safe loop. The system is safe only when ALL components match entity parameters AND the installation respects IEC 60079-14.
Entity parameter matching
The full chain : Ui (transmitter) ≥ Uo (barrier), Ii ≥ Io, Pi ≥ Po, Ci + Cc(cable) ≤ Co, Li + Lc ≤ Lo. Must hold under all credible fault conditions.
FISCO
Fieldbus Intrinsically Safe Concept. Pre-defined trunk parameters for Foundation Fieldbus / PROFIBUS PA segments. Any FISCO-certified device can be added without recalculation. Game-changer for fieldbus IS deployments since 1999.
FNICO
Fieldbus Non-Incendive Concept. Zone 2 only variant of FISCO. Less stringent but limited zone applicability.
System documentation
Every IS system requires a documentation file proving entity parameter compliance. Becomes part of the technical file of the installation.

Notes & guidance

Why systems need their own standard

IEC 60079-11 certifies devices. IEC 60079-25 ensures that when you connect those devices together, the resulting LOOP is also safe. This is non-trivial because :

  1. Cable capacitance / inductance adds up : a 500m cable contributes ~50 nF Ci and ~0.5 mH Li to the loop
  2. Multiple devices on a segment (fieldbus) : each device’s Ci and Pi compounds
  3. Faults can propagate : a fault in one device on a segment could trip another

The 2003 standard formalized the rules. The 2010 revision incorporated FISCO which had become the dominant fieldbus IS pattern.

Loop verification — the 5-point check

For every IS loop in your installation :

1. Ui (device) ≥ Uo (barrier)
2. Ii (device) ≥ Io (barrier)
3. Pi (device) ≥ Po (barrier)
4. Ci (device) + Cc (cable) ≤ Co (barrier)
5. Li (device) + Lc (cable) ≤ Lo (barrier)

If all 5 hold → loop is intrinsically safe. Document and proceed. If any fails → re-engineer the loop (different barrier, shorter cable, lower Ci device).

For typical 24V DC 4-20 mA loops with modern barriers and modern transmitters, the parameters usually have plenty of margin. Problems arise with :

  • Very long cable runs (> 500m start to need careful capacitance check)
  • High-power loops (> 30V or > 100mA)
  • Multi-drop HART loops (multiple Ci values summed)

FISCO simplification

Pre-1999, every fieldbus segment was a custom IS calculation. Each device added meant redoing the math. FISCO defined a standardized “envelope” :

FISCO Foundation Fieldbus standard trunk parameters :
- Trunk voltage : 17.5 V max
- Trunk current : 380 mA max
- Trunk inductance : 5 mH max
- Trunk capacitance : Ci of devices summed must stay within 5 µF
- 30 W max trunk power

Within these limits, add or move FISCO devices freely. The only check needed : total quiescent current of all devices ≤ available supply. Massive simplification of fieldbus design.

Almost all process fieldbus segments in modern plants are FISCO-based. The exceptions (custom IS calculations) are mostly legacy and slowly being migrated.

IS systems in safety functions (SIS)

When the IS loop is part of a safety-instrumented function (SIF) per IEC 61511, additional considerations apply :

  • Barrier failure mode : zener barrier vs galvanic isolator have different failure modes
  • Diagnostic coverage : modern isolators report short / open / earth fault to DCS — credit-able as DC in PFD calculations
  • Common cause : a single barrier failure affecting multiple SIF inputs creates β-factor concerns

Modern safety practice often pairs galvanic isolators (better diagnostics, no earth dependency) with redundant SIL-rated transmitters for SIL 2 / SIL 3 SIFs.

Betroffene Branchen

  • All process industries (instrumentation IS loops everywhere)

Referenzen & Vertiefung