IndustryHub
OVERVIEW / TOOLS & CALCULATORS / ELECTRICAL

Fuse / Breaker Sizing — IEC 60364

Fuse / Breaker Sizing — IEC 60364

Recommended fuse or circuit breaker rating (A) given the load current and cable section, with cable capacity check (Iz) per IEC 60364-5-52.

Recommended rating (A)
Cable capacity (Iz) (A)
IEC 60364 verdict
Formule
COORDINATION RULE

  I_load  ≤  In  ≤  Iz                    (IEC 60364-4-43)

  Variables :
    I_load    load current in normal operation (A)
    In        standard rated current of the protection device (A)
              → first standard value ≥ I_load
    Iz        continuous current capacity of the cable (A)
              → depends on cross-section and installation method

  Rationale : the first inequality (I_load ≤ In) ensures that the
  protection does not trip during normal operation. The second
  (In ≤ Iz) ensures the cable is not overloaded before the protection
  operates. If In > Iz, the cable could burn before the protection
  trips — fire hazard.


STANDARD RATINGS

  In (A) :  6 — 10 — 13 — 16 — 20 — 25 — 32 — 40 — 50 — 63 — 80 — 100
            → 125 — 160 — 200 — 250 — 315 — 400 — 500 — 630 — 800 — 1000

  Rationale : IEC standard values. Always pick the first one greater
  than or equal to I_load. For domestic circuit breakers, the common
  ratings are 10 A (lighting) / 16 A (sockets on 2.5 mm²) /
  20 A (sockets on 4 mm²) / 32 A (cooking).


DO NOT CONFUSE

  In   →  rated current (A, continuous, normal operation)
  Icu  →  ultimate breaking capacity (kA — max Isc the device can interrupt)
  Icw  →  short-time withstand current (kA · s)

  Rationale : three distinct quantities. In sizes the overload
  protection ; Icu must be ≥ prospective Ik3 at the installation point ;
  Icw concerns withdrawable breakers and selectivity with downstream
  protections.

Reference: IEC 60364-4-43, IEC 60364-5-52

Coordination IEC 60364-4-43 : I_load ≤ In ≤ Iz I_loadLoad currentInRatingIzCable capacity↑ does not trip↑ cable not overloadedIn = first standard value ≥ I_load · Iz depends on cross-section + install method

Returns the recommended standard rating for the protective device (fuse or MCB) based on the load current, and verifies that the chosen cable section can carry it (Iz check per IEC 60364-5-52 simplified table).

Note: The Iz values used here assume Copper / PVC insulation / multi-core cable in air at 30°C (method B2). For different installation methods or temperatures, consult the full IEC 60364-5-52 tables and apply the appropriate correction factors.