Search across standards, tools, articles, lessons and the glossary.
↑↓ navigate↵ openEsc close
Fuse / Breaker Sizing — IEC 60364
Recommended fuse or circuit breaker rating (A) given the load current and cable section, with cable capacity check (Iz) per IEC 60364-5-52.
Recommended rating (A)—
Cable capacity (Iz) (A)—
IEC 60364 verdict—
Formule
COORDINATION RULE I_load ≤ In ≤ Iz (IEC 60364-4-43) Variables : I_load load current in normal operation (A) In standard rated current of the protection device (A) → first standard value ≥ I_load Iz continuous current capacity of the cable (A) → depends on cross-section and installation method Rationale : the first inequality (I_load ≤ In) ensures that the protection does not trip during normal operation. The second (In ≤ Iz) ensures the cable is not overloaded before the protection operates. If In > Iz, the cable could burn before the protection trips — fire hazard.STANDARD RATINGS In (A) : 6 — 10 — 13 — 16 — 20 — 25 — 32 — 40 — 50 — 63 — 80 — 100 → 125 — 160 — 200 — 250 — 315 — 400 — 500 — 630 — 800 — 1000 Rationale : IEC standard values. Always pick the first one greater than or equal to I_load. For domestic circuit breakers, the common ratings are 10 A (lighting) / 16 A (sockets on 2.5 mm²) / 20 A (sockets on 4 mm²) / 32 A (cooking).DO NOT CONFUSE In → rated current (A, continuous, normal operation) Icu → ultimate breaking capacity (kA — max Isc the device can interrupt) Icw → short-time withstand current (kA · s) Rationale : three distinct quantities. In sizes the overload protection ; Icu must be ≥ prospective Ik3 at the installation point ; Icw concerns withdrawable breakers and selectivity with downstream protections.
Reference: IEC 60364-4-43, IEC 60364-5-52
Returns the recommended standard rating for the protective device (fuse or MCB) based on the load current, and verifies that the chosen cable section can carry it (Iz check per IEC 60364-5-52 simplified table).
Note: The Iz values used here assume Copper / PVC insulation / multi-core cable in air at 30°C (method B2). For different installation methods or temperatures, consult the full IEC 60364-5-52 tables and apply the appropriate correction factors.