- Design verification
- IEC 61439-1 requires that every assembly design is verified — either by prototype testing (most rigorous), by calculation (e.g., thermal and short-circuit), or by comparison with a reference design already tested. Design verification is the responsibility of the Original Equipment Manufacturer (OEM), not the panel builder using a system.
- Routine verification
- Tests carried out on every completed assembly before delivery — includes wiring check, dielectric test, insulation resistance, protective circuit continuity. Not the same as design verification. Routine tests are mandatory for every unit.
- Form of separation
- Defines how busbars and functional units are physically separated within an assembly. Form 1 = no separation; Form 2 = busbars separated from functional units; Form 3 = functional units separated from each other; Form 4 = terminals separated from functional units. Form 3b and 4b are standard for industrial MCCs.
- Rated short-time withstand current (Icw)
(Icw) - The RMS current an assembly can carry for a defined duration (typically 1 second) without damage. Must be ≥ the prospective short-circuit current at the busbar — the critical parameter for coordinating panel rating with upstream protection.
- Rated peak withstand current (Ipk)
(Ipk) - The peak (instantaneous) current the assembly can withstand. Related to Icw by a factor n (typically 1.5–2.2 depending on power factor). Must be verified against the asymmetric fault current at the panel supply point.
- Internal arc classification (IAC)
(IAC) - Optional classification for assemblies designed to contain and direct the pressure wave from an internal arc fault. Relevant for high-power MCCs and primary switchboards where operator safety during fault is critical (IEC 62271-200 covers MV equivalent).